        PLC programming

        Explain scan behavior, test machine sequences and diagnose control faults using evidence.

        • 6 scenarios
        • 25 minutes each
        • Speak or type your answers
        • A report at your level

        A computer voice asks the questions.

        Your interview level

        Practice scenarios

        Choose a scenario. Each interview ends with a report for the level you selected.

        25 min4 stagesMid level

        Scan order and a retained request

        At Cedar Packing, one task reads a fixed input image, runs top to bottom, then transfers its output image. Its first statement assigns Motor from RunMemory. Its second sets RunMemory from Start. Start changes from false to true before scan 1, and both stored values begin false. Reason through the first two scans without changing the program.

        Start interview
        Rubric and preparationWhat a mid answer covers · 1 lesson to prepare

        Mid standard

        • Motor reads the prior memory value before the second statement updates it, so a Start drop before scan 2 leaves Motor true for that scan and clears RunMemory.
        • I check every writer and cross-reference before reordering because another routine or task can change the value; the last assignment here only explains this specified sequence.
        • I compare false, true, held true and false requests with explicit expected rows because a slow trend can miss a one-scan pulse or retained output.
        25 min4 stagesMid level

        A stop that loses to a start

        Juniper Labels uses RunMemory to remember a start request. A start branch sets it, a stop branch resets it, and a process permit must be true for Motor. A trace shows Start and Stop true together while RunMemory becomes true. The process permit is ordinary control logic, separate from the machine safety system.

        Start interview
        Rubric and preparationWhat a mid answer covers · 1 lesson to prepare

        Mid standard

        • I use one explicit state assignment or exclusive branches and inspect every writer because a later start assignment could overwrite an earlier reset in the same scan.
        • For this proposed policy I clear RunMemory on permit loss and require a released then pressed Start before restart, so a held request can't resume the motor automatically.
        • I restore the permit with Start still held, then release and press it because the motor must remain off until the fresh request under the proposed policy.
        25 min4 stagesMid level

        An interrupted start delay

        At Rowan Filling, a teaching TON timer has a 300 ms preset and gains 100 ms on each enabled scan. Its input is true for scans 1 and 2, false for scan 3, then true for scans 4, 5 and 6. Q is read after the timer call. Explain the expected delay and how you would test a complaint that it starts too soon.

        Start interview
        Rubric and preparationWhat a mid answer covers · 1 lesson to prepare

        Mid standard

        • The recorded ET sequence is 100, 200, 0, 100, 200 and 300 ms under the stated teaching model, so enabled scans separated by an interruption can't be added together.
        • I inspect instance reuse and call order before blaming the preset because a skipped call or another writer can preserve or replace the state observed by later logic.
        • I repeat the interrupted sequence with a different preset and retain every expected ET and Q row because only checking the final output would hide accumulated time from an earlier pulse.
        25 min4 stagesMid level

        A sensor held through a batch reset

        Alder Cartons counts parts with a CTU instance and a preset of 3. With reset false, its CU input is false, true, true, false, true, false, true across seven scans. Next, reset is true for one scan while CU stays true, then reset falls while CU remains true. The specified instance gives reset priority and updates its edge memory on every call.

        Start interview
        Rubric and preparationWhat a mid answer covers · 1 lesson to prepare

        Mid standard

        • I keep the held true input as one event because a second count requires a false-to-true transition; Q uses greater than or equal to the preset.
        • I then lower and raise CU to get CV one because the contract needs a fresh edge; I confirm reset-edge behavior in the actual controller documentation before porting it.
        • I investigate input filtering, bounce and supported hardware counting before changing logic because a software edge detector can't recover an event absent from its input history.
        25 min4 stagesMid level

        A motor command without feedback

        Willow Handling records one row per task completion. At rows 10, 11 and 12, Request, Permit and MotorCommand are true while MotorFeedback is false. At row 13, MotorFeedback becomes true. The HMI said stopped until row 13. The trace has no electrical measurements, input quality flags or documented feedback timeout.

        Start interview
        Rubric and preparationWhat a mid answer covers · 1 lesson to prepare

        Mid standard

        • I keep contactor failure as a hypothesis because the same trace could reflect expected travel delay, an input fault or a wrong feedback binding without any electrical proof.
        • I retain synchronized timestamps, quality and task periods before interpreting the lag because different update rates can make correctly connected signals appear out of order.
        • I write expected outcomes for feedback just before, at and after that boundary, command removal and missing input quality because those cases determine when an alarm should appear and clear.
        25 min4 stagesMid level

        A running-line change and its release checks

        Maple Assembly requests a new process permissive on a running line. The proposed revision must inhibit the ordinary output whenever Permit is false, including during an active cycle. The line owner has not approved an interruption window or a rollback plan. You have an offline program copy and simulated traces, with no connection to physical equipment.

        Start interview
        Rubric and preparationWhat a mid answer covers · 1 lesson to prepare

        Mid standard

        • I identify affected routines, retained state and safety interfaces for review before a download because a protective-function change requires its own qualified design and validation process.
        • I test simultaneous stop and start, permit restoration and retained-state startup against agreed expected results because the new inhibit mustn't silently change restart behavior.
        • I require an approved window, recovery state and rollback trigger before intervention because restoring software alone may not restore safe physical conditions; the approved response may require remaining stopped.

        Interview Hub access

        The Interview Hub is included in All Access. Choose a plan or sign in to your account to continue.

        View plansSign in or join

        Your Work Gym account

        Save your progress and pick up on another device. Your browser's progress comes with you.

        or

        You can keep practicing without an account.

        Help and feedback

        Ask a question, tell us what is not working, or share an idea. We reply by email.

        What is it about?

        We use it only to reply to you.