An HMI number must read the intended live controller tag. Its label and display format do not establish that connection. A wrong binding can look plausible when two process readings happen to match. Change the target independently of the other analog inputs, include zero, and watch the displayed value rather than just its caption.
Bind the display identifier to its exact tag rather than a similarly named raw input. Give the intended tag and the wrong candidate different values during the check. The number must change when only the intended tag changes. Zero is a useful test because a stale display can otherwise look like a plausible measurement.
Read the tag list and the requested sequence before editing.