A negated contact passes the logical path when its tag is false. This is a test of a stored bit. It does not tell you whether a physical device uses normally closed wiring. Read the tag definition first, then test both states so a reversed stop request does not remain hidden.
For a stop-request tag, false means that no stop is requested. A negated contact therefore allows the output while that tag is false. Reverse the input after the first successful scan. An inverted contact can appear correct if you test only the condition that happens to be open initially.
Read the tag list and the requested sequence before editing.