Recovery needs separate evidence that the process cause cleared and that an authorized reset occurred. Keep a fault latched while its cause remains present, even if reset is pressed repeatedly. After clearance, require a new reset before removing the fault record. This preserves the difference between a disappearing signal and a completed recovery.
A disappearing cause does not itself acknowledge the recorded incident. Conversely, an acknowledgment cannot repair a cause that remains active. Test both facts with separate input changes. The final reset is accepted only after clearance. A direct copy of the cause loses the record, while an unconditional reset conceals an active fault.
Read the tag list and the requested sequence before editing.