TOF turns its output on as soon as the input is true. The delay begins when the input falls, so the output remains on during the hold interval. A renewed input cancels that pending switch-off. Test the falling edge and the interrupted hold separately; replacing TOF with TON changes both parts of the behavior.
For a fictional cooling fan, the request starts the fan immediately and its removal begins the hold. Restore the request before the hold finishes, then remove it again. The full interval should be available after that second falling edge. A shortened preset fails immediately before the intended switch-off boundary.
Read the tag list and the requested sequence before editing.